Sensor nodes publish only the sensors that are actually wired
An unwired expander input reads as "clear", so publishing the whole pin table would tell the orchestrator a block is empty using a wire that doesn't exist. Nodes publish an allow-list instead.
- Status
- accepted
- Decided
- Affects
- Layout Feedback
Context
The feedback node’s pin allocation reserves an MCP23017 input for every sensor that will exist. Most aren’t wired
yet. An unwired input sits pulled up, which reads as inactive, which would be published as clear.
For a current-sensing block detector, one clear is enough on its own to let the orchestrator clear the block.
Decision
Allocation is not installation. Each node’s config.py lists the installed sensors, and only those are
published. Bringing a new sensor online is three steps: wire it to its allocated pin, add its id to the installed
list, deploy.
Consequences
- Unwired track reads
unknownin the orchestrator, not falsely empty. - A related weakness is accepted and recorded: a broken wire on an installed sensor also floats up and reads
clear, and re-assertion can’t catch it because the node is alive and still publishing (#9, reopened). That weakness is what the active-high block detector is designed to remove.
Source: layout-feedback CLAUDE.md and
docs/pin-allocation.md.